IPS-DR-120-12 120W DC Power supply 12V 15V 24V 48V DR-120 10A 5A Single group output guide rail industrial power supply 100-240vac
MODEL:IPS-DR-120-12 Rail Power Supply 12v 120w SPECIFICATION: ① AC input: Single-phase 100-240VAC 50/60hz ② DC output: 12VDC, 10A ③ Power: 120W ④ Dimension: 65.5*125*100MM ⑤ NW: 0.79KG

Features:

1. International universal voltage input range: 85-264VAC/120-370VDC

2. Protection type: Short circuit ,Over current ,Over voltage.

3. Natural air cooling

4. Up to 88% work efficiency

5. Standby power consumption as low as 0.3W

6. 100% full load burn-in test

7. 2-year warranty

 

1. Electrical specifications

Module

DR- 120- 12

DR- 120- 15

DR- 120-24

DR- 120-48

 

 

 

 

 

Output characteristic

DC output

12V

15V

24V

48V

Rated current

10A

8A

5A

2.5A

Current range

0-10A

0-8A

0-5A

0-2.5A

Rated power

120W

120W

120W

120W

Ripple&Noise (maximum)

100mVp-p

120mVp-p

150mVp-p

250mVp-p

Voltage adjustment range

10.2-13.8V

13.5-16.5V

21.6-28.8V

43.2-52.8V

Voltage accuracy

± 1%

±1%

±1%

±1%

Linear adjustment rate

± 1%

±1%

±1%

±1%

Load adjustment rate

± 1%

±1%

±1%

±1%

Load adjustment rate

500mS,30mS/230VAC;1000mS,30mS/ 1 15VAC(Full load)

Hold time

30mS/230VAC;10mS/ 1 15VAC (Full load)

 

 

 

Input characteristics

Input voltage

90- 132VAC/ 180-264VAC(Selected by switch)      240-375V DC(Switch on 230VAC)

Input frequency

47-63HZ

Efficiency

85%

85%

87%

88%

Input current

2.6A/ 1 15VAC     1.6A/230VAC

power factor

0.65/ 1 15VAC   0.5/230VAC

Surge current

55A/230VAC

Surge current

<1.0mA/240VAC

 

 

Protective characteristics

Over load protection

110% -180% of rated power

Protection mode: Hiccup protection, automatically restored after abnormal conditions are removed

Over current protection

14-17V

18-22V

28-33V

55-65V

Protection mode: Turn off the output voltage and automatically recover after removing abnormal conditions

Short circuit protection

Short circuit between positive and negative poles at the output end

Protection mode: Hiccup protection, automatically restored after abnormal conditions are removed

 

Environmental

Working temperature

-30℃~70℃(Refer to the derating curve)

Working humidity

20~90%RH No condensation

Storage temperature/humidity

-40℃~85℃ 10~95%RH,No condensation

Anti vibration

10~500HZ, 5G 10 minutes/cycle, X, Y, Z each 60 minutes

 

 

Safety and electromagnetic compatibility

Withstand voltage

Input to output: 1.5KVAC

Insulation impedance

Input to output: 100Ohms/500V DC/25 ℃/70% RH

Electromagnetic compatibility emission

Compliant with EN55032 class A

Electromagnetic compatibility immunity

Compliant with EN61000-4-2

Safety regulations

Complies with GB4943

Others

Product size

65.5*125*100(L*W*H)

Package(KG)

0. 79kg/pcs

Notes

1. All parameters, unless otherwise specified, are measured at 230VAC voltage input, rated load, and 25 ℃ conditions.

2. Ripple and noise voltage are applied at the end of a 12 inch twisted pair oscilloscope with a bandwidth of 20MHz and an additional 0.1 μ And 47 μ The capacitance is measured at a bandwidth of 20MHZ. 3. Accuracy: including setting error, linear adjustment rate, and load adjustment rate.

4. In the case of low input voltage, it is necessary to derate the output. Please refer to the static characteristic curve for details.

5. The startup time is measured during cold start, and frequent switching on and off may increase the startup time.


WhatsApp
Wechat
Contact Us
Your Name:
Your Email:
Your Message:
This website uses cookies to enhance user experience and to analyze performance and traffic on our website.
We also share information about your use of our site with our social media, advertising and analytics partners.
Do Not Sell My Personal Information
Accept Cookies