Product Categories

AC DC Power Supply

IPS-HDR-60-24 HDR Series 60W AC-DC 5V 12V 15V 24V 48V Ultra Slim Step Shape DIN Rail Switching Power Supply
MODEL:IPS-HDR-60-24 Rail Power Supply 24v 60w SPECIFICATION: ① AC input: Single-phase 100-240VAC 50/60hz ② DC output: 24VDC,2.5A ③ Power: 60W ④ Dimension: 52.5*90*54.5MM ⑤ NW: 0.154KG

Features:

1. International universal voltage input range: 85-264VAC/120-370VDC

2. Protection type: Short circuit ,Over current ,Over voltage.

3. Natural air cooling

4. Up to 88% work efficiency

5. Standby power consumption as low as 0.3W

6. 100% full load burn-in test

7. 2-year warranty

 

Electrical specifications

MODEL

HDR-60-5

HDR-60-12

HDR-60-15

HDR-60-24

HDR-60-48

 

 

 

 

OUTPUT

DC VOLTAGE

5V

12V

15V

24V

48V

RATED CURRENT

6.5A

4.5A

4A

25A

1.25A

CURRENT RANGE

0-6.5A

0-4.5A

0-4A

0~2.5A

0-1.25A

RATED POWER

32.5W

54W

60W

60W

60W

RIPPLE &NOISE(max)Note2

80mVp-p

120mVp-P

120mNp-P

150mVp-p

240mVp-P

VOLTAGE ADJ.RANGE

5.0~5.5V

10.8~13.8V

13.5~18V

21.6-29V

432-55.2V

VOLTAGE TOLERANCE Note.3

±2.0%

±1.0%

±1.0%

±1.0%

±1.0%

UNE REGULATION

±1.0%

±1.0%

±1.0%

±1.0%

±1.0%

LOAD REGULATION

±1.0%

±1.0%

±1.0%

±1.0%

±1.0%

SETUP,RISE TIME

500ms,50ms/230VAC    500ms,50ms/115VAC at ful load

HOLD UPTME(Typ.)

30ms/230VAC   12ms/115VAC at full load

 

INPUT

VOLTAGE RANGE

85-264VAC(277VAC operational ) 120-370VDC(390VDC operational

FREQUENCY RANGE

47~63Hz

EFFICIENCY (Typ.)

85%

88%

89%

90%

91%

AC CURRENT (Typ.)

12A/115VAC    0.8A/230VAC

INRUSH CURRENT (Typ.)

COLD START 30N/115VAC    60A/230VAC

 

 

PROTECTON

OVERLOAD

105-160% rated output power

Hiccup mode when output voltage <50%,recovers automatically after fault condition is removed

Constant current limiting within 50%-100%rated output voltage,recovers automatically after fault condition is removed

OVER VOLTAGE

5.75~6.75V

14.2~16.2V

18.8~22.5V

30-36V

56.5~648V

Protection type:Shut down o/p voltage,re-power on to recover

 

BWROMMENT

WORKING TEMP

-30~+70℃(Refer to 'Derating Curve"

WORKING HUMIDITY

20~90%RH non-condensing

STORAGE TEMP,HUMIDITY

40~+85℃,10~96%RH non-condensation

TEMP.COEFFICIENT

±0.03%/C(0~50℃)RH non-condensing

VIBRATION

10~500Hz,2G 10min/cycle,period for 60min.each along X,Y,Z axes;Mounting Compliance to IEC60068-2-6

OPERATING    ALTITUDE

2000 meters

OVER VOLTAGE CATEGORY

Ⅲ;According to EN61558,EN50178,EN60664-1,EN62477-1;altitude up to 2000 meters

 

 

 

 

 

 

SAFETY&

EMC

Note 4)

SAFETY STANDARDS

UL62368-1,UL508,TUV BS EN/EN61558-2-16.BS EN/EN61558-1,IEC62368-1,EAC TP TC 004,BSMI CNS14336-1, IS13252(Part1)IIEC60950-1 approved;Design refer to BS EN/EN62368-1

WITHSTAND VOLTAGE

UP-OP4KVAC

ISOLATION RESISTANCE

UP-O/P:100M Ohms 1500VDC125 C170%RH

 

EMC EMISSION

Parameter

Standard

Test Level/Note

Conducted

BS EN/EN55032(CISPR32).CNS13438

Class B

Radiated

BS ENEN55032(CISPR32),CNS13438

Class B

Harmonic Current

BS EN/EN61000-3-2

Class A

Voltage Flicker

BS EN/EN61000-3-3


 

 

 

EMC IMMUNITY

BS EN/EN55024,BS EN/EN55035,BS EN/EN61000-6-2,BS EN/EN61204-3

Parameter

Standard

Test Level /Note

ESD

BS EN/EN61000-4-2

Level 3,8KV air,Level 2,4KV contact,criteria A

Radiated Susceptibility

BS EN/EN61000-4-3

Level 3,criteria A

EFT/Burest

BS EN/EN61000-4-4

Level 3,criteria A

Surge

BS EN/EN61000-4-5

Level4,2KV/L-N,criteria A

Conducted

BS EN/EN61000-4-6

Level 3,criteria A

Magnetic Field

BS EN/EN61000-4-8

Level4,criteria A

Voltage Dips and interruptions

BS EN/EN61000-4-11

>95%dip0.5periods,30%dip 25 periods >95%interruptions 250 periods

OTHERS

MTBF

927.6K hrs min.MILHDBK-217F(25℃)

DMENSION

52.5*90*54.5mm (WH'D)

PACKING

190g,60pcs'124Kg10.97CUFT


WhatsApp
Wechat
Contact Us
Your Name:
Your Email:
Your Message:
This website uses cookies to enhance user experience and to analyze performance and traffic on our website.
We also share information about your use of our site with our social media, advertising and analytics partners.
Do Not Sell My Personal Information
Accept Cookies