Product Categories

IPS-LNGC280-5K-DTL 5KW Hydro Generator Grid-Tied Inverter Small Hydro Turbine Grid Converter Run-of-River Hydro Converter
①Model: IPS-LNGC280-5K-DTL ②AC INPUT (Generator): 1-phase 2-wire 0-350VAC (customizable) ③AC OUTPUT (Grid): 1-phase 2-wire 220VAC±15% 50/60HZ±10% or Customize ④Maximum equipment power: 5.5KW ; Rated equipment power: 5KW ⑤Application: Small-scale hydraulic power stations (≤5KW), distributed single-phase hydraulic power grid connection, rural household hydropower generation (or customized for different areas) ⑥Adjusting method: Color touchscreen, switchable between Chinese and English, integrated display and control, and clear display of operating data ⑦Power factor ≥0.99, MPPT voltage range 100-280VAC, THD <3% (rated power), standby power consumption <100W ⑧Protection features include reverse polarity protection, short circuit protection, islanding protection, overheating protection, and overload protection

Single-phase hydraulic grid-connected inverter

Model

LNGC-*KDTL

Rated Power (KW)

5

10

15

30

50

75

100

200

AC Input Voltage Range

0-350VAC (☆Other voltages available upon request)

MPPT Voltage Range

100-280VAC (☆Other voltages available upon request)

Rated Input Current (A)

13.2

26.3

39.4

78.8

131.3

196.9

262.5

524.9

Maximum Input Current (A)

14.5

28.9

43.4

86.7

144.3

216.6

288.7

577.4

Rated AC Output Power (KW)

5

10

15

30

50

75

100

200

Maximum AC Output Power (KW)

5.5

11

16

33

55

82

110

220

Current Harmonic THD

<3% (of rated power)

Power Factor

≥0.99

Maximum Efficiency

High frequency 99%; Power frequency 96%

Rated Output Voltage and Frequency

220VAC 50/60Hz (☆Other voltages and frequencies available upon request)

Allowable Grid Voltage Range

±15% (☆Other voltages available upon request)

Allowable Grid Frequency Range

±10% (☆Other frequencies available upon request)

Standby Power Consumption

<100W

Automatic Operation Conditions

DC input and grid requirements are met, and the inverter operates automatically.

Automatic Restart Time After Power Failure

5 minutes (time is adjustable)

Protection Functions

Reverse polarity, short circuit, islanding, overheating, overload, etc.

Display Method

Touch screen

Wind Turbine Power Curve

30 power points can be set

Operating Temperature

-10℃~+50℃ (☆Other temperatures can be customized)

Relative Humidity

0-90% (non-condensing)

Altitude

≤6000m. Derating is required above 2000 meters (1% derating for every 100 meters increase)

Cooling Method

Forced air cooling

Noise

<65dB (at 1m distance)

Protection Class

IP20 (☆Customizable to IP54)

Communication Protocol

Modbus RTU/ Modbus TCP


Three-phase hydraulic power grid-connected converter

Model

LNGC-*KSTL

Rated Power (KW)

10

30

50

100

250

500

750

1000

AC Input Voltage Range

0-550Vac (Other voltages available upon request)

MPPT Voltage Range

250-500Vac (Other voltages available upon request)

Rated Input Current (A)

15.2

45.6

76

152

379.9

759.7

1139.6

1519.4

Maximum Input Current (A)

16.8

50.2

83.6

167.2

417.9

835.7

1253.5

1671.4

Rated AC Output Power (KW)

10

30

50

100

250

500

750

1000

Maximum AC Output Power (KW)

11

33

55

110

275

550

825

1100

Current Harmonic THD

<3% (of rated power)

Power Factor

≥0.99

Maximum Efficiency

High frequency 99%; Power frequency 96%

Rated Output Voltage and Frequency

380V 50/60Hz (☆Other voltages and frequencies available upon request)

Allowable Grid Voltage Range

±15% (☆Other voltages available upon request)

Allowable Grid Frequency Range

±10% (☆Other frequencies available upon request)

Standby Power Consumption

<100W

Automatic Operation Conditions

DC input and grid requirements are met, and the inverter operates automatically.

Automatic Restart Time After Power Failure

5 minutes (time is adjustable)

Protection Functions

Reverse polarity, short circuit, islanding, overheating, overload, etc.

Display Method

Touch screen

Wind Turbine Power Curve

30 power points can be set

Operating Temperature

-10℃~+50℃ (☆Other temperatures can be customized)

Relative Humidity

0-90% (non-condensing)

Altitude

≤6000m. Derating is required above 2000 meters (1% derating for every 100 meters increase)

Cooling Method

Forced air cooling

Noise

<65dB (at 1m distance)

Protection Class

IP20 (☆Customizable to IP54)

Communication Protocol

Modbus RTU/ Modbus TCP


WhatsApp
Wechat
Contact Us
Your Name:
Your Email:
Your Message:
This website uses cookies to enhance user experience and to analyze performance and traffic on our website.
We also share information about your use of our site with our social media, advertising and analytics partners.
Do Not Sell My Personal Information
Accept Cookies