Single-phase hydraulic grid-connected inverter | |||||||||
Model | LNGC-*KDTL | ||||||||
Rated Power (KW) | 5 | 10 | 15 | 30 | 50 | 75 | 100 | 200 | |
AC Input Voltage Range | 0-350VAC (☆Other voltages available upon request) | ||||||||
MPPT Voltage Range | 100-280VAC (☆Other voltages available upon request) | ||||||||
Rated Input Current (A) | 13.2 | 26.3 | 39.4 | 78.8 | 131.3 | 196.9 | 262.5 | 524.9 | |
Maximum Input Current (A) | 14.5 | 28.9 | 43.4 | 86.7 | 144.3 | 216.6 | 288.7 | 577.4 | |
Rated AC Output Power (KW) | 5 | 10 | 15 | 30 | 50 | 75 | 100 | 200 | |
Maximum AC Output Power (KW) | 5.5 | 11 | 16 | 33 | 55 | 82 | 110 | 220 | |
Current Harmonic THD | <3% (of rated power) | ||||||||
Power Factor | ≥0.99 | ||||||||
Maximum Efficiency | High frequency 99%; Power frequency 96% | ||||||||
Rated Output Voltage and Frequency | 220VAC 50/60Hz (☆Other voltages and frequencies available upon request) | ||||||||
Allowable Grid Voltage Range | ±15% (☆Other voltages available upon request) | ||||||||
Allowable Grid Frequency Range | ±10% (☆Other frequencies available upon request) | ||||||||
Standby Power Consumption | <100W | ||||||||
Automatic Operation Conditions | DC input and grid requirements are met, and the inverter operates automatically. | ||||||||
Automatic Restart Time After Power Failure | 5 minutes (time is adjustable) | ||||||||
Protection Functions | Reverse polarity, short circuit, islanding, overheating, overload, etc. | ||||||||
Display Method | Touch screen | ||||||||
Wind Turbine Power Curve | 30 power points can be set | ||||||||
Operating Temperature | -10℃~+50℃ (☆Other temperatures can be customized) | ||||||||
Relative Humidity | 0-90% (non-condensing) | ||||||||
Altitude | ≤6000m. Derating is required above 2000 meters (1% derating for every 100 meters increase) | ||||||||
Cooling Method | Forced air cooling | ||||||||
Noise | <65dB (at 1m distance) | ||||||||
Protection Class | IP20 (☆Customizable to IP54) | ||||||||
Communication Protocol | Modbus RTU/ Modbus TCP | ||||||||
Three-phase hydraulic power grid-connected converter | |||||||||
Model | LNGC-*KSTL | ||||||||
Rated Power (KW) | 10 | 30 | 50 | 100 | 250 | 500 | 750 | 1000 | |
AC Input Voltage Range | 0-550Vac (Other voltages available upon request) | ||||||||
MPPT Voltage Range | 250-500Vac (Other voltages available upon request) | ||||||||
Rated Input Current (A) | 15.2 | 45.6 | 76 | 152 | 379.9 | 759.7 | 1139.6 | 1519.4 | |
Maximum Input Current (A) | 16.8 | 50.2 | 83.6 | 167.2 | 417.9 | 835.7 | 1253.5 | 1671.4 | |
Rated AC Output Power (KW) | 10 | 30 | 50 | 100 | 250 | 500 | 750 | 1000 | |
Maximum AC Output Power (KW) | 11 | 33 | 55 | 110 | 275 | 550 | 825 | 1100 | |
Current Harmonic THD | <3% (of rated power) | ||||||||
Power Factor | ≥0.99 | ||||||||
Maximum Efficiency | High frequency 99%; Power frequency 96% | ||||||||
Rated Output Voltage and Frequency | 380V 50/60Hz (☆Other voltages and frequencies available upon request) | ||||||||
Allowable Grid Voltage Range | ±15% (☆Other voltages available upon request) | ||||||||
Allowable Grid Frequency Range | ±10% (☆Other frequencies available upon request) | ||||||||
Standby Power Consumption | <100W | ||||||||
Automatic Operation Conditions | DC input and grid requirements are met, and the inverter operates automatically. | ||||||||
Automatic Restart Time After Power Failure | 5 minutes (time is adjustable) | ||||||||
Protection Functions | Reverse polarity, short circuit, islanding, overheating, overload, etc. | ||||||||
Display Method | Touch screen | ||||||||
Wind Turbine Power Curve | 30 power points can be set | ||||||||
Operating Temperature | -10℃~+50℃ (☆Other temperatures can be customized) | ||||||||
Relative Humidity | 0-90% (non-condensing) | ||||||||
Altitude | ≤6000m. Derating is required above 2000 meters (1% derating for every 100 meters increase) | ||||||||
Cooling Method | Forced air cooling | ||||||||
Noise | <65dB (at 1m distance) | ||||||||
Protection Class | IP20 (☆Customizable to IP54) | ||||||||
Communication Protocol | Modbus RTU/ Modbus TCP | ||||||||