Introduction to IDEALPLUSING High Voltage DC Power Supply
Introduction to High Voltage Direct Current

1.png

Brief Introduction

        The voltage of the high-voltage DC power supply is within 0-50KV, and the power can reach 400kW.

The voltage and current can be continuously adjusted, and it can work continuously and stably at full load for a long time.

        This power supply can be used in high-tech tests in national defense, gas discharge, and test aging of high-voltage electron tubes, and can also be used in test aging of other electronic components.

        Since the output voltage of this power supply is relatively high, unless otherwise specified, the output negative terminal is generally connected to the chassis, that is, the ground wire, to ensure the personal safety of the user.

 简单,高级,高清,白色背景,玻璃倒影.png

Performance characteristics

● Specification range: nearly 200 specifications, output voltage 800-50kV, output current 0-200A, output power 6-400kW optional

● Constant voltage and constant current: voltage value is continuously adjustable from 5% to 100% of the rated value, current is continuously adjustable from zero to the rated value, constant voltage and constant current are automatically converted

● Overvoltage protection: voltage protection value is continuously adjustable from 0 to 110% of the rated value, and the power supply will trip when the output voltage exceeds the voltage protection value

● Short circuit protection: rated voltage below 2KV is allowed Short circuit is allowed, short circuit tripping protection above 2KV

● Overload protection: When the power supply or load fails and the output current exceeds 1.5 times the rated value, the power supply trips for protection

● Short circuit alarm: When the output is short-circuited, the power supply will sound and light alarm (optional)

● Automatic discharge: for capacitive load shutdown and discharge (optional)

● Output display: voltage and current are displayed simultaneously on LED digital tubes (standard); LCD display (optional)

● Pulse operation: can be equipped with a time controller to form a pulse power supply (optional)

● Intelligent Energy: can be connected to a computer to form a computer-controlled intelligent power supply (optional)

● Analog signal interface: users can use 0~5V or 4~20mA signals to control the output voltage and current of the power supply (optional)

 你的段落文字 (2).png

Main uses

● Colleges and universities, laboratories of scientific research institutes, electrical product testing and debugging

● Electronic product testing, aging, gas discharge

● Routine testing of electronic components

● Power supply for klystrons, magnetrons, and electron guns

● High-voltage capacitor charging power supply

● Whole machine aging and all other occasions where high voltage output is required

 

Technical indicators

Stable voltage and current

 

Voltage is continuously adjustable from 5%-10% rated value to 100% rated value

Current value is continuously adjustable from approximately 0 to rated 

value, and the voltage and current are automatically switched

Voltage regulation accuracy

 

Source effect: ≤0.1% rated value (rate of change of output voltage caused by 

input power supply voltage change ±10%)

Time drift: ≤0.3% rated value (rate of change of output voltage caused by 

continuous operation of the power supply for more than 8 hours)

Temperature drift: ≤0.04% rated value/℃ (rate of change of output voltage 

caused by ambient temperature change within the ambient temperature 

range of power supply use)

Load effect: ≤0.3% (rate of change of output voltage caused by output current of 

the power supply changing from zero to rated value)

Steady current accuracy

 

Source effect: ≤0.1% rated value (rate of change of output current caused by 

input power supply voltage change ±10%)

Time drift: ≤1% rated value (rate of change of output current caused by 

continuous operation of the power supply for more than 8 hours)

Temperature drift: ≤0.04% rated value/℃ (rate of change of output current caused by ambient temperature change within the ambient temperature range of power 

supply use)

Load effect: ≤0.3% rated value (rate of change of output current caused by output voltage change from zero to rated value)

Output ripple

 

Positive high voltage, negative grounding: ≤0.2%+10mV (measured at 80%~

100% rated output)

Negative high voltage, positive grounding: ≤0.1%+10mV (measured at 80%~

100% rated output)

Voltage/current setting

Ten-turn potentiometer (standard); button setting optional

Display mode

 

Voltage and current meter LED digital tube display (standard); LCD liquid crystal display (optional)

Display resolution

LED: Voltage meter 0.1V, current meter 0.01A or 1mA (Note: the display accuracy of different specifications of power supplies may be different)

LCD: 4-digit display (Note: the display accuracy of different specifications of 

power supplies may be different)

Display error

≤±1%±1 digit (measurement range 5%~50% rated value)

≤±0.5%±1 digit (measurement range 50%~100% rated value)

Short circuit protection

Rated voltage below 2KV allows short circuit, above 2KV trip protection

Protection mode

Overvoltage, overcurrent, phase loss automatic protection

Working mode

Long-term full-load continuous operation

Input voltage

Three-phase AC380V±10%  50Hz/60Hz±10%

Environmental conditions

Temperature -20℃-+40℃   Humidity ≤80%