Features:
1. International universal voltage input range: 85-264VAC/120-370VDC
2. Protection type: Short circuit ,Over current ,Over voltage.
3. Natural air cooling
4. Up to 88% work efficiency
5. Standby power consumption as low as 0.3W
6. 100% full load burn-in test
7. 2-year warranty
1.Electrical specifications
MODULE | HDR-100-5 | HDR-100-12 | HDR-100-15 | HDR-100-24 | HDR-100-48 | |
Output characteristic | DC output voltage | 5V | 12V | 15V | 24V | 48V |
Rated current | 10A | 7.1A | 6. 13A | 3.83A | 1.92A | |
Current range | 0- 10A | 0-7.1A | 0-6.13A | 3.83A | 0- 1.92A | |
Rated power | 50W | 85.2W | 92W | 92W | 92.2W | |
Ripple&Noise (maximum) | 80mVp-p | 150mVp-p | 150mVp-p | 200mVp-p | 240mVp-p | |
Voltage adjustment range | 4.5-5.5V | 10.8-13.8V | 13.5-18V | 21.6-26.4V | 43.2-55.2V | |
Voltage accuracy | ± 2% | ± 1% | ± 1% | ±1% | ± 1% | |
Linear adjustment rate | ± 1% | ± 1% | ± 1% | ±1% | ± 1% | |
Load adjustment rate | ± 1% | ± 1% | ± 1% | ±1% | ± 1% | |
Start&Rise Time | 2000mS,30mS/ 1 15VAC(Full load);1500mS ,30mS/230VAC | |||||
Hold time | 30mS/230VAC (Full load) 10mS/ 1 15VAC (Full load) | |||||
Input characteristics | input voltage | 85-264VAC 120-370V DC | ||||
Input frequency | 47-63Hz | |||||
efficiency | 82% | 85% | 86% | 88% | 88% | |
Input current | 0.88A/ 1 15VAC 0.48/230VAC | |||||
power factor | 0.65/230VAC(Full load) | |||||
Surge current | 40A/230VAC (Cold start) | |||||
Protective characteristics | Over load protection Over current protection | 10% -130% of rated power | ||||
Protection mode: Hiccup protection, automatically restored after abnormal conditions are removed | ||||||
Short circuit protection working temperature | 10% -130% of rated current | |||||
Protection mode: Hiccup protection, automatically restored after abnormal conditions are removed | ||||||
Working humidity Storage temperature/humidity | Short circuit between positive and negative poles at the output end | |||||
Protection mode: Hiccup protection, automatically restored after abnormal conditions are removed | ||||||
Environmental | Anti vibration | -30 ℃~70 ℃ (refer to the derating curve) | ||||
Withstand voltage | 20~90% RH without condensation | |||||
Insulation impedance | -40 ℃~85 ℃ 10~95% RH, no condensation | |||||
Electromagnetic compatibility emission | 10~500HZ, 5G 10 minutes/cycle, X, Y, Z each 60 minutes | |||||
Safety and electromagnetic compatibility | Electromagnetic compatibility immunity | Input to output: 800VAC | ||||
Safety regulations | Input to output: 100M hms/500V DC/25 ℃/70% RH | |||||
DMENSION | 70*90*54.5mm(L*W*H) | |||||
PACKING | 0.27kg/pcs | |||||
Notes | 1. All parameters, unless otherwise specified, are measured at 230VAC voltage input, rated load, and 25 ℃ conditions. 2. Ripple and noise voltage are applied at the end of a 12 inch twisted pair oscilloscope with a bandwidth of 20MHz and an additional 0.1 μ And 47 μ The capacitance is measured at a bandwidth of 20MHZ. 3. Accuracy: including setting error, linear adjustment rate, and load adjustment rate. 4. In the case of low input voltage, it is necessary to derate the output. Please refer to the static characteristic curve for details. 5. The startup time is measured during cold start, and frequent switching on and off may increase the startup time. |