model | LUD-D- | |||||
1K | 10K | 30K | 45K | 60K | ||
DC input | Rated Voltage V | 220 | ||||
Voltage Range V | 180—300 | |||||
AC input | Rated Voltage V | 220V/380V | ||||
Voltage Range V | 220/380±15% | |||||
Frequency Range Hz | 45—65 | |||||
Power Factor PF | 0.9 | |||||
Bypass input | Input Voltage Range | 220±15%VAC | ||||
Input Rated Current A | 4.5 | 45 | 136 | 202.5 | 272 | |
Switching time | Bypass↔Inverter ms | ≤4 | ||||
Mains↔DC Panel ms | 0 | |||||
AC output | Rated Capacity KVA | 1 | 10 | 30 | 45 | 60 |
Rated Voltage V | 220Vac | |||||
Rated Frequency Hz | 50Hz | |||||
Rated Current A | 4.5 | 45 | 136 | 202.5 | 272 | |
Voltage Accuracy V | 220V±3% | |||||
Frequency Accuracy Hz | 50Hz±0.05Hz | |||||
THD | ≤3%(Linear load) | |||||
Dynamic Response Load 0~100% | 5% | |||||
Power Factor (PF) | 0.8 | |||||
Overload Capacity | 150%,10 seconds | |||||
Crest Factor CF | 3:1 | |||||
Inverter Efficiency | 90%(80% resistive load) | |||||
Working Env. Temp. | Withstand Voltage Requirements (Input/Output) | 2000Vac,1 minute | ||||
Noise (1 meter) | ≤50db | |||||
Operating Ambient Temp. | -10℃~~+50℃ | |||||
Humidity | 0~~90%,No condensation | |||||
Operating Altitude m | ≤2000 | |||||
Protection functions | Complete protection features include input reverse polarity and undervoltage protection, output overload and short-circuit protection, and over-temperature protection. | |||||
Other | It uses a power frequency isolation transformer, provides a pure sine wave output, is completely stable, and has a strong load capacity. | |||||
model | LUD-D- | |||||
5K | 10K | 50K | 100K | 200K | ||
DC input | Rated Voltage V | 220 | ||||
Voltage Range V | 180—300 | |||||
AC input | Rated Voltage V | 220V/380V | ||||
Voltage Range V | 220/380±15% | |||||
Frequency Range Hz | 45—65 | |||||
Power Factor PF | 0.9 | |||||
Bypass input | Input Voltage Range | 380±15%VAC | ||||
Input Rated Current A | 7.6 | 15.2 | 76 | 152 | 304 | |
Switching time | Bypass↔Inverter ms | ≤4 | ||||
Mains↔DC Panel ms | 0 | |||||
AC output | Rated Capacity KVA | 5 | 10 | 15 | 30 | 45 |
Rated Voltage V | 380Vac (3-phase 4-wire) | |||||
Rated Frequency Hz | 50Hz | |||||
Rated Current A | 7.6 | 15.2 | 76 | 152 | 304 | |
Voltage Accuracy V | 380V±3% | |||||
Frequency Accuracy Hz | 50Hz±0.05Hz | |||||
THD | ≤3%(Linear load) | |||||
Dynamic Response Load 0~100% | 5% | |||||
Power Factor (PF) | 0.8 | |||||
Overload Capacity | 150%,10 seconds | |||||
Crest Factor CF | 3:1 | |||||
Inverter Efficiency | 90%(80% resistive load) | |||||
Working Env. Temp. | Withstand Voltage Requirements (Input/Output) | 2000Vac,1 minute | ||||
Noise (1 meter) | ≤50db | |||||
Operating Ambient Temp. | -10℃~~+50℃ | |||||
Humidity | 0~~90%,No condensation | |||||
Operating Altitude m | ≤2000 | |||||
Protection functions | Complete protection features include input reverse polarity and undervoltage protection, output overload and short-circuit protection, and over-temperature protection. | |||||
Other | It uses a power frequency isolation transformer, provides a pure sine wave output, is completely stable, and has a strong load capacity. | |||||
model | LUG-D- | |||||
6K | 10K | 30K | 75K | 100K | ||
DC input | Rated Voltage V | 384 | ||||
Voltage Range V | 300—480 | |||||
AC input | Rated Voltage V | 220V/380V | ||||
Voltage Range V | 220/380±15% | |||||
Frequency Range Hz | 45—65 | |||||
Power Factor PF | 0.8 | |||||
Switching time | Bypass↔Inverter ms | ≤4 | ||||
Mains↔DC Panel ms | 0 | |||||
AC output | Rated Capacity KVA | 6 | 10 | 30 | 75 | 100 |
Rated Voltage V | 200VAC | |||||
Rated Frequency Hz | 50Hz | |||||
Voltage Accuracy V | 220V±3% | |||||
Frequency Accuracy Hz | 50Hz±0.05Hz | |||||
THD | ≤3%(Linear load) | |||||
Dynamic Response Load 0~100% | 5% | |||||
Power Factor (PF) | 0.8 | |||||
Overload Capacity | 150%,10 seconds | |||||
Crest Factor CF | 3:1 | |||||
Inverter Efficiency | 90%(80% resistive load) | |||||
Working Env. Temp. | Withstand Voltage Requirements (Input/Output) | 2000Vac,1 minute | ||||
Noise (1 meter) | ≤50db | |||||
Operating Ambient Temp. | -10℃~~+50℃ | |||||
Humidity | 0~~90%,No condensation | |||||
Operating Altitude m | ≤2000 | |||||
Protection functions | Complete protection features include input reverse polarity and undervoltage protection, output overload and short-circuit protection, and over-temperature protection. | |||||
Other | It uses a power frequency isolation transformer, provides a pure sine wave output, is completely stable, and has a strong load capacity. | |||||
model | LUG-S- | |||||
10K | 30K | 50K | 75K | 100K | ||
DC input | Rated Voltage V | 384 | ||||
Voltage Range V | 300—480 | |||||
AC input | Rated Voltage V | 380V | ||||
Voltage Range V | 380±15% | |||||
Frequency Range Hz | 45—65 | |||||
Power Factor PF | 0.8 | |||||
Switching time | Bypass↔Inverter ms | ≤4 | ||||
Mains↔DC Panel ms | 0 | |||||
AC output | Rated Capacity KVA | 10 | 30 | 50 | 75 | 100 |
Rated Voltage V | 380VAC | |||||
Rated Frequency Hz | 50Hz | |||||
Voltage Accuracy V | 380V±3% | |||||
Frequency Accuracy Hz | 50Hz±0.05Hz | |||||
THD | ≤3%(Linear load) | |||||
Dynamic Response Load 0~100% | 5% | |||||
Power Factor (PF) | 0.8 | |||||
Overload Capacity | 150%,10 seconds | |||||
Crest Factor CF | 3:1 | |||||
Inverter Efficiency | 90%(80% resistive load) | |||||
Working Env. Temp. | Withstand Voltage Requirements (Input/Output) | 2000Vac,1 minute | ||||
Noise (1 meter) | ≤50db | |||||
Operating Ambient Temp. | -10℃~~+50℃ | |||||
Humidity | 0~~90%,No condensation | |||||
Operating Altitude m | ≤2000 | |||||
Protection functions | Complete protection features include input reverse polarity and undervoltage protection, output overload and short-circuit protection, and over-temperature protection. | |||||
Other | It uses a power frequency isolation transformer, provides a pure sine wave output, is completely stable, and has a strong load capacity. | |||||